FCPK 2-8 CONVENTIONAL CONTROL PANELS

FCPK2-8The FCPK 2-8 Fire Alarm Control Panel is a flexible, expandable conventional system available from 2 to 8 zones.

The panel is designed to be aesthetically pleasing with a contrasting membrane facia incorporating tactile controls with a key switch override and matches the other panels in the range. The FCPK 2-8 control panel can greatly reduce wiring installation costs by utilising its unique 2-Wire zone configuration. This allows sounders to be wired on the same trigger zone circuit, therefore eliminating the need for the sounder circuitry wiring.

FPG-Control-Equipment

FEATURES

  • Available from 2 to 8 zone
  • Designed to comply with BS5839 pt 4 1988 and EN54 pts 2 & 4
  • Programmable microprocessor based system
  • Enclosure is manufactured from high quality steel, available with optional flush bezel.
  • Has built in power supply and charger unit, accepts 2 No. 12 volt 6 Ampere hour batteries
  • One man commissioning – allows trigger devices and sounders to be automatically reset after alarm initiation.
  • Zone configuration allows for conventional or Sav-Wire working per zone.
  • Zone Isolation – allowing individual zones to be disabled for maintenance or other work to be carried out. During zone isolation, the zone sounders are still active.
  • Zone Alarm isolation – allowing the zone alarms to be disabled whilst the detection for that zone is still active.
  • De-latch facility to allow non-latching of individual zones with or without alarms.
  • A maximum of 7 Active AND 7 passive repeaters may be connected to the panel
SPECIFICATIONFCPK 2-8 CONTROL PANELS
Panel Dimensions385mm wide, 310mm high, 95mm deep
Operating Voltage230V 50Hz AC (UK) – other voltages available
Power Supply3 Amp maximum output
Sounder Output2 short and open circuit protected monitored outputs
500 mA output per conventional sounder circuit. Total 1.6A max
Auxiliary Relay2 x Volt free changeover contacts 1 Amp 24V max. per relay
Detector CircuitSav-Wire to operate with Sav-Wire type detector bases
Maximum Devices20 per zone
2-Wire alarm zoneOptional 350 mA max alarm load per zone
Devices SupportedAll Apollo, Hochiki, Nittan and most other manufacturers detectors. Please check for details
Quiescent Current65mA (2 Zone), 93mA (8 Zone)
Display8 LED zone Fire indicators, 8 LED zone Fault indicators, 1 LED common Fire indicators
KeyboardMembrane click action tactile 11 keys
FasciaContrasting grey colour as standard, other options available
Number of zones2 – 8 as standard
Additional Equipment2 way sounder expansion card, 4 wire repeater panel, Auxiliary Dual Relay PCB’s, Multi-function Timer PCB, Modem driver PCB’s for connection to the BT network, Line I/O unit
Auxiliary OutputsCommon Fire, Common Fault, 24v supply
Auxiliary InputsRing Bells (Class Change) (COV), Reset, Silence Alarms (SAL)