PAGER INTERFACE
The Pager Interface is a programmable interface providing connectivity of third party paging systems to the MxPro 5 control equipment.
It utilises the industry standard protocol ESPA 4.4.4 and connects to the equipment via a serial data connection. An optional input function is available to monitor pager fault conditions. Specific event types (e.g. Fire, Alarm, Pre- Alarm, Fault, etc.) can be sent to individual pagers and/or to groups of pagers.
Applications / Limitations
For use with pager systems compliant to ESPA 4.4.4 protocol. If a printer is also required, fit an internal printer assembly.
LITERATURE
FEATURES
- Up to 8 configurable shifts per weekday/weekend
- Up to 50 pager groups
- Up to 250 pager addresses
- Each pager address can be configured to cover 2 zone ranges
- Zone and/or point information can be sent to the pager
- User defined texts are available and the basic event type text can be configured
- ESPA 4.4.4 protocol
- Panel mounted or boxed version
- Easily configured via pager PC Software
- 3 year warranty as standard
SPECIFICATION | PAGER INTERFACE |
---|---|
Power Supply | 15-30V DC (e.g. wired from panel 24V auxiliary supply) |
Supply Current | 100mA (typical at 24V DC) |
Temperature | -5°C to 50°C |
Humidity | 95% humidity (non condensing) |
Dimensions H x W x D mm | Enclosure: 218 x 300 x 45 |
Pager Interface | RS232 galvanically (opto) isolated |
Fault Input | Non-monitored/monitored (10K EOL, 470R active) |
Event Types Supported | Fire Alarm, Test Alarm, Plant Alarm, Pre-Alarm, Fault and Disablement |