MAC 1-4 FIRE ALARM CONTROL PANELS

FPG-MAC-1-4The MAC 1-4 Analogue Addressable Fire Alarm Control Panels offer true analogue fire sensing. The success of the MAC 1-4 systems lie in their ability to be totally flexible and cater for the exact needs of each individual site it is applied to.

They have been designed to be flexible, expandable analogue addressable systems to exceed the demands of the current market requirements. Indeed the system can cater from a single loop panel to a multi- loop networked system, utilising standard equipment.

Its proven ability to distinguish real fires from false alarms with speed and accuracy ensures complete peace of mind for both the specifiers and end users of the system.

FPG-MAAC

FEATURES

  • Optional flush mounting unit and glazed lockable door
  • Optional Deep back-box option
  • Integrated, tactile, alpha numeric keypad
  • 240 x 60 Graphical back lit liquid crystal display
  • 1000 Fire, Fault and Diagnostic Event Log
  • Optional on-board or remote printer
  • Network capabilities
  • Manufactured from high quality steel, available in a range of finishes
  • Available as 1 to 2 Loop and 1 to 4 Loop Panels
  • Ability to support Hochiki, Apollo XP95 & Discovery protocols
  • Optional 25, 50 and 100 LED zonal fire and fault indicators
  • Multiple panel units available for 5 to 28 loops

ORDERING INFORMATION

  • MAC 1/2 1 loop panel expandable to 2 loops with 2 on-board Alarm Lines
  • MAC 2/2 2 loop panel with 2 on-board Alarm Lines
  • MAC 1/4 1 loop panel expandable to 4 loops with 4 on-board Alarm Lines
  • MAC 2/4 2 loop panel expandable to 4 loops with 4 on-board Alarm Lines
  • MAC 3/4 3 loop panel expandable to 4 loops with 4 on-board Alarm Lines
  • MAC 4/4 4 loop panel with 4 on-board Alarm Lines
  • (add ‘D’ for deep back-box i.e. MAC 2/4/D)

STANDARDS

The MAC 1-2 and MAC 1-4 Panels conform to the following standards:

  • BS5839-4 with optional Zonal Fire LED’s
  • BS EN54-2 Control and Indicating Equipment
  • BS EN54-4 Power Supply Equipment
  • BS EN60950 Safety of information technology equipment
  • BS EN50130-4: 196 Product Family Standard
  • EMC Directive 89/336/EEC (and the amending directive 92/23/EEC)
  • Low Voltage Directive 73/23/EEC
SPECIFICATIONMAC 1-2MAC 1-4
Dimensions475 H x 450 W x 115 D475 H x 450 W x 115 D
Deep Back-box475 H x 450 W x 188 D475 H x 450 W x 188 D
Recessed475 H x 450 W x 100 D (173 D (L))475 H x 450 W x 100 D ( 173 D (L))
Loops1-21-4
Loop Current500mA500mA
Power Supply4/5 Amp Switch Mode4 / 5 Amp Switch Mode
Charger Current2A DDP monitored2A DDP monitored
Sounder Circuits2 x 1Amp Programmable4 x 1Amp Programmable
Relays2 x 1Amp 30v max2 x 1Amp 30v max
Weight10.5 Kg10.5 Kg
Serial ports1 x RS2321 x RS232
Prog Inputs88
Prog Outputs88
Battery CapacityInternal max 18 Ahr, External max 48 AhrInternal max 18 Ahr, External max 48 Ahr
Number of Zones10001000
ApprovalsBS EN54-2 & 4:1998BS EN54-2 & 4:1998