MAAC 2-8 FIRE ALARM CONTROL PANELS

FPG-MAAC-2-8The MAAC 2-8 series is fully expandable from 2 to 8 loops and supplied with 8 on-board sounder circuits, 20 programmable Zonal LEDs with slide-in labels, and 25 System LEDs for information purposes. There are also 8 programmable function buttons with LED indication for confirmation of operation.

The control panel consists of the latest dual flash-based microprocessor technology combined with a high resolution, high contrast, graphical LCD display and tactile keypad providing a simple select & click programming aid for engineer configuration and end-user operation.

Powerful cause-and-effect programming coupled with dynamic zoning, and enhanced Trace Diagnostics makes the panel suitable for a wide range of site applications from small to large complex multi-area systems. Fully programmable onsite via the on-board alphanumeric keypad, or PC-NeT configuration software.

FPG-MAAC

FEATURES

  • Fully expandable from 2 – 8 loops via plug-in loop driver boards.
  • 20 programmable Zonal / 25 System LED’s with slide-in labels.
  • Advanced graphical LCD user interface and support for up to 200 fire zones by default allowing full EN54 compliance without additional hardware expansion.
  • Dual flash-based microprocessor technology with Real-Time Clock on-board.
  • Dedicated USB & RS232 Serial Port for direct PC or modem connection.
  • Installer friendly ‘Auto-learn’, ‘Loop Detection’ and on-board Scope facility for ease of Commissioning and Fault finding. Fully programmable via the on-board alphanumeric keypad, or PC configuration tools.
  • Integral ‘P-Bus’ for system expansion via available option cards.
  • Connection to the ‘Ad-NeT’ peer-to-peer network is achieved using a simple plug-in network card allowing the system to share up to 2000 zones with full cross panel reporting, control and site-wide cause and effect functionality.
  • Approved to BS EN54 part 2, 4 and 13.

ORDERING INFORMATION

  • MAAC 2/8 2 loop panel expandable to 8 loops with 8 on-board Alarm Lines
  • MAAC 3/8 3 loop panel expandable to 8 loops with 8 on-board Alarm Lines
  • MAAC 4/8 4 loop panel expandable to 8 loops with 8 on-board Alarm Lines
  • MAAC 5/8 5 loop panel expandable to 8 loops with 8 on-board Alarm Lines
  • MAAC 6/8 6 loop panel expandable to 8 loops with 8 on-board Alarm Lines
  • MAAC 7/8 7 loop panel expandable to 8 loops with 8 on-board Alarm Lines
  • MAAC 8/8 8 loop panel with 8 on-board Alarm Lines
  •  (add ‘D’ for deep back-box i.e. MAAC 2/4/D)

STANDARDS

The MAAC 1-4 Panel conform to the following standards:

  • BS EN54-2 Control and Indicating Equipment
  • BS EN54-4 Power Supply Equipment
  • BS EN60950 Safety of information technology equipment
  • BS EN50130-4: 196 Product Family Standard
  • EMC Directive 89/336/EEC
  • (and the amending directive 92/23/EEC)
  • Low Voltage Directive 73/23/EEC
SPECIFICATIONMAAC 2-8 FIRE ALARM CONTROL PANELS
Dimensions Normal Enc750 H x 450 W x 190 D
Loops2-8
Loop current500mA
Power Supply3 Amp Switch Mode
Charger Current2 A DDP monitored
Sounder Circuits8 x 1Amp Programmable
Relays4 x 1Amp 30v max
Serial ports2 x RS232, 2 x USB
Prog Inputs2 / 16 (M,L,D)
Zone LED’s with cards20
Battery Capacity2 x 24v 18Ah Internal / 1x 24v 45Ah Internal and 1x 24v 45Ah External
Number of Zones2000
Zone LED’s with cards20
Battery CapacityInternal 7Ahr / 12Ahr (M) / 18Ahr (L) / 45Ahr (D)
Number of Zones2000