MAAC 1 FIRE ALARM CONTROL PANELS

MAAC-1-PanelThe MACC 1 Series of control panels are supplied with a single loop driver card, 2 on-board Sounder Circuits, 20 programmable Zonal LED’s with slide-in labels, and 25 System LED’s for information purposes.

There are also 4 programmable function buttons with LED indication for confirmation of operation.

The control panel consists of the latest dual flashbased microprocessor technology combined with a high resolution / high contrast Graphical LCD display and tactile keypad providing a simple ‘Select & Click’ programming aid for Engineer configuration and End-User operation. Powerful Cause and Effect programming coupled with ‘DynamiX’ zoning, and enhanced ‘Trace Diagnostics’ makes the panel suitable for a wide range of site applications from small to large complex multi-area systems.

Fully programmable on-site via the on-board alphanumeric keypad, or PC-NeT Configuration Software.

FPG-MAAC

FEATURES

  • 20 programmable Zonal / 25 System LED’s with slide-in labels.
  • Advanced graphical LCD user interface and support for up to 200 fire zones by default allowing full EN54 compliance without additional hardware expansion.
  • Dual flash-based microprocessor technology with Real-Time Clock on-board.
  • Installer friendly ‘Auto-learn’, ‘Loop Detection’ and on-board Scope facility for ease of Commissioning and Fault finding. Fully programmable via the on-board alphanumeric keypad, or PC configuration tools.
  • Robust removable equipment chassis with plug-in connectors for simple fixing and cable termination.
  • Connection to the ‘Ad-NeT’ peer-to-peer network is achieved using a simple plug-in network card allowing the system to share up to 2000 zones with full cross panel reporting, control and site-wide cause and effect functionality.
  • Approved to BS EN54 part 2, 4 and 13.

STANDARDS

The MAAC 1 Panel conform to the following standards:

  • BS EN54-2 Control and Indicating Equipment
  • BS EN54-4 Power Supply Equipment
  • BS EN60950 Safety of information technology equipment
  • BS EN50130-4: 196 Product Family Standard
  • EMC Directive 89/336/EEC
  • (and the amending directive 92/23/EEC)
  • Low Voltage Directive 73/23/EEC
SPECIFICATIONMAAC 1 FIRE ALARM CONTROL PANELS
Dimensions Normal Enc340 H x 340 W x 85 D
Dimensions Medium (M)340 H x 430 W x 115 D
Dimensions Large (L)470 H x 450 W x 115 D
Dimensions Deep (D)470 H x 450 W x 190 D
Loops1
Loop current500mA
Power Supply3 Amp Switch Mode
Charger Current1A DDP monitored
Sounder Circuits2 x 1Amp Programmable
Relays2 x 1Amp 30v max
Weight6/7 Kg
Serial ports1 x RS232, 1 x USB
Prog Inputs1 / 8 (M,L,D)
Zone LED’s with cards20
Battery CapacityInternal 7Ahr / 12Ahr (M) / 18Ahr (L) / 45Ahr (D)
Number of Zones2000