MAAC 1 FIRE ALARM CONTROL PANELS
The MACC 1 Series of control panels are supplied with a single loop driver card, 2 on-board Sounder Circuits, 20 programmable Zonal LED’s with slide-in labels, and 25 System LED’s for information purposes.
There are also 4 programmable function buttons with LED indication for confirmation of operation.
The control panel consists of the latest dual flashbased microprocessor technology combined with a high resolution / high contrast Graphical LCD display and tactile keypad providing a simple ‘Select & Click’ programming aid for Engineer configuration and End-User operation. Powerful Cause and Effect programming coupled with ‘DynamiX’ zoning, and enhanced ‘Trace Diagnostics’ makes the panel suitable for a wide range of site applications from small to large complex multi-area systems.
Fully programmable on-site via the on-board alphanumeric keypad, or PC-NeT Configuration Software.
LITERATURE
FEATURES
- 20 programmable Zonal / 25 System LED’s with slide-in labels.
- Advanced graphical LCD user interface and support for up to 200 fire zones by default allowing full EN54 compliance without additional hardware expansion.
- Dual flash-based microprocessor technology with Real-Time Clock on-board.
- Installer friendly ‘Auto-learn’, ‘Loop Detection’ and on-board Scope facility for ease of Commissioning and Fault finding. Fully programmable via the on-board alphanumeric keypad, or PC configuration tools.
- Robust removable equipment chassis with plug-in connectors for simple fixing and cable termination.
- Connection to the ‘Ad-NeT’ peer-to-peer network is achieved using a simple plug-in network card allowing the system to share up to 2000 zones with full cross panel reporting, control and site-wide cause and effect functionality.
- Approved to BS EN54 part 2, 4 and 13.
STANDARDS
The MAAC 1 Panel conform to the following standards:
- BS EN54-2 Control and Indicating Equipment
- BS EN54-4 Power Supply Equipment
- BS EN60950 Safety of information technology equipment
- BS EN50130-4: 196 Product Family Standard
- EMC Directive 89/336/EEC
- (and the amending directive 92/23/EEC)
- Low Voltage Directive 73/23/EEC
SPECIFICATION | MAAC 1 FIRE ALARM CONTROL PANELS |
---|---|
Dimensions Normal Enc | 340 H x 340 W x 85 D |
Dimensions Medium (M) | 340 H x 430 W x 115 D |
Dimensions Large (L) | 470 H x 450 W x 115 D |
Dimensions Deep (D) | 470 H x 450 W x 190 D |
Loops | 1 |
Loop current | 500mA |
Power Supply | 3 Amp Switch Mode |
Charger Current | 1A DDP monitored |
Sounder Circuits | 2 x 1Amp Programmable |
Relays | 2 x 1Amp 30v max |
Weight | 6/7 Kg |
Serial ports | 1 x RS232, 1 x USB |
Prog Inputs | 1 / 8 (M,L,D) |
Zone LED’s with cards | 20 |
Battery Capacity | Internal 7Ahr / 12Ahr (M) / 18Ahr (L) / 45Ahr (D) |
Number of Zones | 2000 |
Approvals | EN 54-2:1998, EN 54-4:1998 & EN 54-13:2005 |