WWS HI POWER ADDRESSABLE WALL WAFER SOUNDER

WWS-Wall-SounderThe WWS is a Loop Powered Wall Fire Alarm Sounder which is fully compatible with Hochiki’s ESP analogue addressable protocol.

The WWS comprises of a low current sounder allowing solid state addressing remotely by using the ASX Programmer. A selection of tones are available and the unit can be driven continuously or pulsed under full synchronisation of the control panel and hence all sounders will pulse at the same time.

FPG-AnalogueAlarms

FEATURES

  • Single Loop Address
  • Loop addresses 1 – 127
  • Loop Powered
  • Fits Standard Analogue Detector
  • 90 to 102dB (A) output
  • Low current consumption
  • Available in weather proof version to IP65 with WP base
SPECIFICATIONWWS HI POWER ADDRESSABLE WALL WAFER SOUNDER
ColourRed / White
Ordering CodeWWS or WWS/WP wall mount sounder
Operating VoltageLoop 17-41 Vdc
Quiescent Current150μ A
Alarm Current2mA – 8mA max
Sounder Output90 – 102dB (A)
Transmission MethodDigital Communications Using ESP
Operating Temp. Range-10°C to + 50°C
Storage Temp. Range-30°C to + 70°C
Maximum Humidity95%RH – Non Condensing (at 40°C)
IP RatingIP21 / IP65 (weatherproof version)
ApprovalsLPCB & VdS