VIGILON INTERFACES
LITERATURE
FEATURES
- Modern aesthetic design
- IP40 ingress Protection
- Input monitor selection
- Lockable door
- Approved to EN54 Parts 2 & 4
Interfaces are used to link the fire alarm system to other plant management devices such as sprinklers and security systems. They can also be used to link to a zone of conventional detectors or non Gent manufactured devices.
Interfaces are either powered from the loop or require a separate mains supply. The mains power version has its own battery backup.
SPECIFICATION | ||||
---|---|---|---|---|
Type | Mains | Loop | Zone Module | Single Channel |
Max number per Loop | 8 | 30 | 100 | 100 |
Approx Weight | 8.6 Kg | 2.4 Kg | 0.7 Kg | 0.7 Kg |
Operating Temperature | 0oC to 45oC | 0oC to 45oC | 0oC to 45oC | 0oC to 45oC |
Ingress Protection | IP44 | IP40 | IP40 | IP40 |
Voltage | 230vAC | Loop Powered | Loop Powered | Loop Powered |
Number of Channels | 3 | 2 | 10 | 10 |
Input Channels | Fire Fault MCP fire OEM detectors | Fire Fault Non-fire event | 2 Wire for conventional zone circuits | Fire Fault Non-fire events |
Case Material | Mild Steel | Mild Steel | Mild Steel | Mild Steel |
Width | 504mm | 270mm | 204mm | 204mm |
Height | 305mm | 261mm | 125mm | 125mm |
Depth | 98mm | 60mm | 50mm | 50mm |